Rittal SK 3304500 230 V enclosure cooling unit with e-Comfort control and condensate evaporation. Check cooling capacity, installation and request a quote.
Item No :
SK 3304500Material :
Sheet steelColor :
RAL 7035Weight :
35.15 kg
Rittal SK 3304500 is a 230 V single-phase Blue e TopTherm wall-mounted cooling unit for electrical enclosures. Its e-Comfort controller regulates cabinet temperature, while the integral electric condensate evaporator handles condensate produced during cooling. The unit provides active cooling where warm ambient air makes fan ventilation insufficient.
Need to confirm cooling capacity or replace an existing unit? Send SUWI Auto the article number, quantity and delivery destination. Include the cabinet heat losses, maximum ambient temperature, target internal temperature and supply frequency. For replacement, add a nameplate photo and existing cut-out dimensions.
| Article no. | SK 3304500 |
| Design | Wall-mounted enclosure cooling unit |
| Dimensions (W × H × D) | 400 × 950 × 260 mm |
| Material | Sheet steel |
| Colour | RAL 7035 |
| Cooling output to DIN EN 14511 | L35/L35, 50 Hz: 1.10 kW L35/L35, 60 Hz: 1.25 kW L35/L50, 50 Hz: 0.91 kW L35/L50, 60 Hz: 0.90 kW |
| Rated operating voltage | 230 V, single-phase, 50/60 Hz |
| Maximum rated current | 50 Hz: 4.1 A 60 Hz: 5.1 A |
| Maximum start-up current | 50 Hz: 12 A 60 Hz: 14 A |
| Air throughput (unimpeded) | External circuit: 805 m³/h Internal circuit: 600 m³/h |
| Energy efficiency ratio at L35/L35 | 50 Hz: 1.67 60 Hz: 1.52 |
| Protection category to IEC 60529 | External circuit: IP34 Internal circuit: IP54 |
| UL type rating | Type 12 |
| Temperature control | e-Comfort controller Factory setting: +35 °C |
| Operating temperature range | +10 °C to +55 °C |
| Temperature setting range | +20 °C to +55 °C |
| Storage temperature range | −40 °C to +70 °C |
| Power consumption | L35/L35, 50 Hz: 0.66 kW L35/L35, 60 Hz: 0.82 kW L35/L50, 50 Hz: 0.77 kW L35/L50, 60 Hz: 0.89 kW |
| Refrigerant / charge | R-513A / 0.325 kg |
| Maximum permissible operating pressure | 28 bar |
| Manufacturer-specified pre-fuse | Miniature circuit-breaker/fuse: 10 A |
| Supply includes | Condenser with hydrophobic RiNano coating Fully wired unit with plug-in terminal strip Drilling template Assembly parts Integral electric condensate evaporation |
| Packaging unit | 1 pc. |
| Net weight | 35.15 kg |
| Gross weight | 38 kg |
| EAN | 4028177322936 |
| ETIM 8 / ETIM 9 | EC000855 |
SK 3304500 provides 1.10 kW at L35/L35 and 0.91 kW at L35/L50 at 50 Hz. L35/L35 means a cabinet internal temperature of 35 °C and ambient air at 35 °C. L35/L50 uses the same internal temperature with ambient air at 50 °C. Use the output at the installation’s design temperatures when selecting the unit.
For example, a calculated cooling duty of 1.0 kW at 35 °C inside and 50 °C outside exceeds this model’s 50 Hz rating. Choose a unit with sufficient capacity at those conditions. Include component heat losses and enclosure heat transfer in the calculation; a drive’s motor power is not its heat loss inside the cabinet.
Choose external, partial internal or full internal mounting using the corresponding Rittal installation drawing. The overall housing dimensions are not the cabinet cut-out dimensions. Check internal clearance, the mounting surface’s load capacity and access for maintenance. For door mounting, also check the hinges, door alignment and sealing.
Keep the internal and external air inlets and outlets clear. Cable ducts, nearby walls and densely packed components can restrict airflow. Confirm the electrical connection and protective device against the unit’s nameplate and installation instructions before commissioning.
The specification table follows Rittal’s R-513A product listing. For an existing unit, check the nameplate and use the instructions matching its refrigerant version. Review the model coverage and conditions in the relevant certificate when an approval is required.
Request an SK 3304500 quotation. Provide the quantity, delivery destination and available supply voltage/frequency. For a replacement, include a nameplate photo and mounting dimensions. For selection support, include cabinet heat losses, maximum ambient temperature and target cabinet temperature. If the existing unit has a fault, also send the display message and measured temperatures.
Compare the Blue e TopTherm series if SK 3304500 does not match the cabinet heat load, available mounting space or power supply. Check each alternative’s cooling output at the required temperatures, mounting dimensions and electrical requirements before changing models.
View Blue e TopTherm Wall-Mounted Cooling Units, 0.3–4 kW