Rittal SK 3329540 TopTherm Blue e Wall-Mounted Cooling Unit

Rittal SK 3329540 three-phase enclosure cooling unit for 400 V/50 Hz or 460 V/60 Hz. Check heat load, mounting and troubleshooting, then request a quote.

  • Item No :

    SK 3329540
  • Material :

    Sheet steel
  • Color :

    RAL 7035
  • Weight :

    70.3 kg
TopTherm wall-mounted cooling unit Blue e 0.3 - 4 kW

Rittal SK 3329540 is a three-phase Blue e TopTherm wall-mounted cooling unit for electrical enclosures with substantial heat losses. Its rated supply is 400 V at 50 Hz or 460 V at 60 Hz. The unit has an e-Comfort controller and integral electric condensate evaporation.

 

Adding drives or replacing an undersized cabinet cooler? Send SUWI Auto the revised cabinet heat losses, supply voltage and frequency, maximum ambient temperature and mounting arrangement. Include the quantity and delivery destination for a quotation.

 

Article no. SK 3329540
Design Wall-mounted enclosure cooling unit
Dimensions (W × H × D) 400 × 1580 × 295 mm
Material Sheet steel
Colour RAL 7035
Cooling output to DIN EN 14511 L35/L35, 50 Hz: 2.55 kW
L35/L35, 60 Hz: 2.75 kW
L35/L50, 50 Hz: 1.90 kW
L35/L50, 60 Hz: 2.00 kW
Rated operating voltage 400 V, three-phase, 50 Hz
460 V, three-phase, 60 Hz
Maximum rated current 50 Hz: 3.3 A
60 Hz: 3.4 A
Maximum start-up current 50 Hz: 6.8 A
60 Hz: 7.6 A
Air throughput (unimpeded) External circuit: 1200 m³/h
Internal circuit: 1200 m³/h
Energy efficiency ratio at L35/L35 50 Hz: 2.11
60 Hz: 1.88
Protection category to IEC 60529 External circuit: IP34
Internal circuit: IP54
UL type rating Type 12
Temperature control e-Comfort controller
Factory setting: +35 °C
Operating temperature range +10 °C to +55 °C
Temperature setting range +20 °C to +55 °C
Storage temperature range −40 °C to +70 °C
Power consumption L35/L35, 50 Hz: 1.19 kW
L35/L35, 60 Hz: 1.46 kW
L35/L50, 50 Hz: 1.45 kW
L35/L50, 60 Hz: 1.75 kW
Refrigerant / charge R-513A / 1.15 kg
Maximum permissible operating pressure 28 bar
Manufacturer-specified protective device Motor circuit-breaker: 6.3–10 A
Supply includes Condenser with hydrophobic RiNano coating
Fully wired unit with plug-in terminal strip
Drilling template and assembly parts
Integral electric condensate evaporation
Packaging unit 1 pc.
Net / gross weight 70.3 kg / 74 kg
EAN 4028177323124
ETIM 8 / ETIM 9 EC000855

 

Size the Unit for the Revised Cabinet Heat Load

Adding drives, power supplies or other equipment can increase cooling demand beyond the original cabinet design. At 50 Hz, SK 3329540 delivers 2.55 kW at L35/L35 and 1.90 kW at L35/L50. These ratings use a 35 °C cabinet temperature with ambient air at 35 °C or 50 °C respectively.

For example, a required duty of 2.2 kW at 35 °C inside and 50 °C outside exceeds the 1.90 kW rating at 50 Hz. Recalculate component heat losses and enclosure heat transfer after modifying the cabinet. Select the cooling unit using its output at the design temperatures.

Check Three-Phase Supply and Mounting Strength

Match the installation supply to the specified voltage and frequency: 400 V, three-phase, 50 Hz or 460 V, three-phase, 60 Hz. Have a qualified electrician confirm phase availability, phase sequence and motor protection against the nameplate and installation manual. The listed 6.3–10 A motor circuit-breaker range does not mean that the breaker should automatically be set to 10 A.

The unit weighs 70.3 kg and is 1580 mm high. Check the mounting surface, door loading, cabinet stability and service clearance. Use the installation drawing for the selected mounting arrangement; the overall housing dimensions are not the cut-out dimensions.

Operating Problems and Practical Checks

Drives remain hot although the display temperature is acceptable +

Check for local hotspots and airflow blocked by cable ducts or equipment. The controller display may not represent the temperature at every component. Restore circulation through the cabinet and compare the revised heat load with the available cooling output.

A phase-related alarm appears after electrical connection +

Record the exact displayed code. Ask a qualified electrician to check the phases and their sequence using the model’s instructions. Correct the supply fault before restarting; repeated resets cannot resolve a missing phase.

Cooling performance falls during hot production shifts +

Measure ambient temperature at the air intake. Inspect condenser contamination, fitted filters and recirculation of hot exhaust air. Restore clear airflow and review cooling capacity at the measured temperature. Isolate the supply before cleaning; trained personnel should carry out servicing.

Condensate builds up in humid conditions +

Check enclosure seals and unnecessary door opening. Avoid setting the temperature lower than the equipment requires. Follow the manual’s drainage arrangement, keeping the discharge hose free from kinks and laid with a continuous fall. Persistent water accumulation requires inspection of the condensate handling system.

Approvals

Downloads

 

Check the certificate scope against the project requirements. For replacement or servicing, use the instructions matching the refrigerant and production version shown on the existing nameplate.

Accessories to Confirm for the Installation

Door monitoring and filter media +

Confirm a compatible door-operated switch where door monitoring is required. Select filter media for the actual dust or oil contamination, and verify the accessory article number for this model.

Condensate handling and monitoring connections +

Integral condensate evaporation is supplied with SK 3329540. Confirm the discharge hose arrangement for the installation. For IoT monitoring, confirm the required Blue e IoT adaptor, IoT interface and connections separately.

Request an SK 3329540 quotation or cooling capacity check. Provide quantity, destination, supply voltage/frequency and cabinet heat losses. Include maximum ambient temperature, target internal temperature and mounting details. For replacement, add the existing nameplate photo and cut-out dimensions; for a fault, include the controller message and measured temperatures.

 

Compare Other Cooling Outputs and Supply Options

If the available supply, installation space or calculated cooling duty does not match SK 3329540, compare other Blue e TopTherm models. Confirm the alternative’s output at the design temperatures and its mounting requirements before changing the cabinet layout.

View Blue e TopTherm Wall-Mounted Cooling Units, 0.3–4 kW

 

Get a Free Quote
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.

Related Products

Rittal AE 1034500 Wall-Mounted Enclosure
Rittal AE 1034500 Wall-Mounted Enclosure

Rittal AE 1034500 steel enclosure, 300 × 400 × 210 mm, with mounting plate, IP66 protection and NEMA 4 rating.

Read More
Rittal AE 1035500 Wall-Mounted Enclosure
Rittal AE 1035500 Wall-Mounted Enclosure

Rittal AE 1035500 steel enclosure, 200 × 300 × 155 mm, with mounting plate, IP55 protection and NEMA 12 rating.

Read More
Rittal AE 1036500 Wall-Mounted Enclosure
Rittal AE 1036500 Wall-Mounted Enclosure

Rittal AE 1036500 steel enclosure, 300 × 300 × 155 mm, with mounting plate, IP66 protection and NEMA 4 rating. 

Read More
Rittal AE 1037500 Wall-Mounted Enclosure
Rittal AE 1037500 Wall-Mounted Enclosure

Rittal AE 1037500 steel enclosure, 400 × 800 × 300 mm, with mounting plate, IP66 protection and NEMA 4 rating.

Read More
Rittal AE 1038500 Wall-Mounted Enclosure
Rittal AE 1038500 Wall-Mounted Enclosure

Rittal AE 1038500 steel enclosure, 380 × 600 × 210 mm, with mounting plate, IP66 protection and NEMA 4 rating.

Read More
Rittal  AE 1039500 Wall-Mounted Enclosure
Rittal AE 1039500 Wall-Mounted Enclosure

Rittal AE 1039500 steel enclosure, 600x380x210 mm, with mounting plate, IP66 protection and NEMA 4 rating.

Read More
Rittal SV 9681646 IP55 Roof Plate, 400 × 600 mm
Rittal SV 9681646 IP55 Roof Plate, 400 × 600 mm

Rittal SV 9681646 closed IP55 roof plate for 400 × 600 mm VX and VX IT enclosures. 1.5 mm carbon steel, RAL 7035.

Read More
Rittal SV 9681648 IP55 Roof Plate, 400 × 800 mm
Rittal SV 9681648 IP55 Roof Plate, 400 × 800 mm

Rittal SV 9681648 closed IP55 roof plate for 400 × 800 mm VX and VX IT enclosures. 1.5 mm carbon steel, RAL 7035. 

Read More