The outlet filter is used in conjunction with the corresponding fan-and-filter unit to dissipate heat loss from enclosures, ventilate the enclosure and protect temperature-sensitive components. This is achieved through the direct infeed of ambient air, the temperature of which must be lower than the permissible internal temperature of the enclosure.
Item No :
SK 3240300Material :
PlasticOrder(MOQ) :
1 pc(s).Color :
RAL 7035Weight :
0.4 kgThe Rittal SK 3240300 is a RAL 7035 light-grey Blue e+ outlet filter for SK 3240.7xx, 3240.9xx, 3241.7xx and 3241.9xx fan-and-filter units. Installed in an enclosure wall, it provides a filtered exit for warm internal air while a matching powered fan brings in cooler ambient air. This ventilation path helps release heat from electrical components housed inside.
| Article no.: | SK 3240300 |
| Product | Blue e+ outlet filter |
| Version | Wall-mounted |
| Dimensions | Width: 255 mm (10.04 in) Height: 255 mm (10.04 in) Depth: 45.2 mm (1.78 in) |
| Mounting cut-out | Width: 224 mm (8.82 in) Height: 224 mm (8.82 in) |
| Suitable for model no. | SK 3240.7xx/3240.9xx/3241.7xx/3241.9xx |
| Benefits | Tool-free mounting Optimized snap hooks for faster enclosure installation Opening louvred grille for easier filter changes |
| Material | Plastic |
| Color | RAL 7035 |
| Supply includes | Outlet filter Pleated filter |
| Protection category NEMA | Type 12 with chopped-fibre filter or pleated filter Type 3, 3R, 4 and 4X with chopped-fibre filter or pleated filter and hose-proof hood |
| IP protection category to IEC 60529 | IP54 with chopped-fibre filter or pleated filter IP55 with pleated filter and absorber mat IP56 with chopped-fibre filter or pleated filter and hose-proof hood |
| Packaging unit | 1 pc(s). |
| Net weight | 0.4 kg |
| Gross weight | 0.67 kg |
| Customs tariff number | 39269097 |
| EAN | 4028177998360 |
| ETIM 9 / ETIM 8 | EC002513 |
| ECLASS 8.0 | 27180706 |
Select SK 3240300 when the powered fan is in one of the specified Blue e+ SK 3240 or SK 3241 families and the enclosure requires a RAL 7035 light-grey outlet. The filter has a 255 × 255 mm face and needs a 224 × 224 mm panel opening. Verify both dimensions and the installation clearance on the enclosure drawing.
The supplied pleated filter is accessible through the opening louvred grille, making inspection and filter changes easier during routine maintenance. Optimized snap hooks support tool-free mounting once the panel cut-out has been prepared.
Rittal specifies IP54 and NEMA Type 12 with a pleated filter. The listed IP55 arrangement adds an absorber mat, while the IP56 and NEMA Type 3/3R/4/4X arrangements use a filter with a compatible hose-proof hood. Select the powered fan separately according to enclosure heat loss and operating temperatures.
| Article number | Use it when | Do not treat as interchangeable when |
|---|---|---|
| SK 3240300 | The fan is an SK 3240.7xx, 3240.9xx, 3241.7xx or 3241.9xx and a RAL 7035 outlet is specified. | The finish must be black, the system requires EMC protection, or the cut-out differs from 224 × 224 mm. |
| SK 3240308 | A matching Blue e+ fan uses the same panel opening but the outlet grille must be RAL 9005 black. | The enclosure design calls for the light-grey RAL 7035 version. |
| SK 3240400 | The matching fan is an SK 3240.8xx or 3241.8xx EMC model and the EMC outlet filter is required. | The project uses a standard Blue e+ fan covered by SK 3240300 rather than the EMC arrangement. |
| Item | Relevant customer requirement |
|---|---|
| Pleated replacement filter | Inspect the supplied pleated filter as site dust builds up. Confirm a replacement medium sized for the SK 3240/3241 outlet before ordering. |
| SK 3240.080 stainless steel hose-proof hood 282 × 390 × 85 mm |
For the specified IP56 or NEMA Type 3/3R/4/4X arrangement, check the assembled filter-and-hood configuration and leave room for the hood outside the enclosure. |
| Absorber mat | Rittal specifies IP55 when a pleated filter is used with an absorber mat. Confirm the matching accessory and assembly requirements for the installation. |
For model confirmation or quotation, send: the powered fan article number, enclosure heat loss, maximum ambient temperature, permitted internal temperature, required IP/NEMA rating, installation drawing, quantity and delivery destination. These details allow the outlet, airflow and protection arrangement to be checked together.